11 votes

Can I pass DC 36V 100A through a terminal block that is rated for DC 300V 30A?

The application using a terminal block should keep within all of the block ratings. That is, it should have a lower Voltage, lower Current and lower Power. Now there may be some wriggle room in the ...
Neil_UK's user avatar
  • 174k
11 votes
Accepted

Can I pass DC 36V 100A through a terminal block that is rated for DC 300V 30A?

Your second premise is correct as with any connectors, it can handle only the maximum ratings in each respect alone. So no going over the current spec because the voltage is lower. Study the datasheet ...
Arsenal's user avatar
  • 18.1k
8 votes
Accepted

What kind of terminal block is this?

These are rail-mounted feed-through push-in terminal blocks. You can get them for all kinds of rail systems, the ones I've linked to are for NS15 rails.
Jonathan S.'s user avatar
  • 20.5k
8 votes
Accepted

Are there terminal blocks that are quick to attach for use in a production environment?

The standard way to do this in a manufacturing environment is to use test fixture grabbers (my site). They work with any wire, some even with unstripped wire (they perforate the insulation). {My ...
Davide Andrea's user avatar
8 votes

Are there terminal blocks that are quick to attach for use in a production environment?

There's Wago-clamp style "lever-fixer" screwless terminal blocks. Wago specifies these for stranded and solid wires, bare or crimped to a ferrule. Similar ideas exist in varying degrees of ...
Marcus Müller's user avatar
6 votes

Are there terminal blocks that are quick to attach for use in a production environment?

An exemple a PCB version is available at : https://www.phoenixcontact.com/en-in/new-products/new-products-device-connection-technology/lever-actuated-pcb-terminal-blocks-and-pcb-connectors or https://...
Vincent's user avatar
  • 1,361
4 votes

Best practice for adding Resistor to PLC cabinet

I know this is an old question, but I found a couple more options for this while looking for something similar: I found this from one supplier, haven't found anyone else that makes them. Ocean ...
sandyscott's user avatar
4 votes
Accepted

Best practice for adding Resistor to PLC cabinet

A search for "DIN rail component carrier" throws up images such as this. Figure 1. A user-configurable PCB with screw terminals and DIN rail mount. Image source: Google image search. For just one or ...
Transistor's user avatar
  • 180k
4 votes
Accepted

Using a thermal fuse in a PCB terminal block?

In a commercial project the main disadvantage would be cost. A terminal block requires space and additional space to access it (might not be available at the point where the fuse should sit). And it ...
Arsenal's user avatar
  • 18.1k
3 votes
Accepted

Identifying a connection terminal specification from photo

My Identiconn utility identified it as a Molex Picoblade, 3-wall header. https://www.molex.com/en-us/products/connectors/wire-to-board-connectors/picoblade-connectors {Source - Digikey} EDIT - Plug ...
Davide Andrea's user avatar
3 votes

Are there terminal blocks that are quick to attach for use in a production environment?

If you aren't going directly to a PCB, the Wago 222/221 series are a good option for connecting wires with quick attachment and easy removal. They also make mounting carriers to hold them in place.
kolyur's user avatar
  • 206
3 votes
Accepted

Three-phase motor 380 V wiring

It's a Dahlander, pole-changing, two-speed motor. Here's the schematic. Two terminal blocks have been provided to facilitate motor configuration for either 700 RPM or 1400 RPM. A couple of ...
vu2nan's user avatar
  • 19.2k
3 votes

Looking For a Specific Connector

How about a part like 691508110302. Per the site, it is surface-mount and rated at 10A.
Robert Fay's user avatar
  • 1,226
3 votes
Accepted

How to stack protoboards solidly?

Use male and female headers. Female header with short pins: (Image from grobotronics.com) "Stackable" female header with long pins that go through to the next board (or can be simply cut to length)....
Bort's user avatar
  • 5,242
2 votes
Accepted

Do DIN rail mount interface relay modules with a "spare" terminal exist?

See Phoenix Contact FBST, it's a bar that goes in the slots under the wire connector you see on the blue relay module. Finder will have similar. 093.16 for example. See their catalog. Keep an eye on ...
Jeroen3's user avatar
  • 24k
2 votes
Accepted

12V/5A power through DB9

There are some DB9 connectors with 5A rated pins. Most are 3A rated pins (or higher) Assuming you design for the lower standard your options are use a higher voltage and use a switching regulator to ...
Passerby's user avatar
  • 73.4k
2 votes

What kind of terminal block is this?

I call these "DIN rail terminal blocks". They are made by Phoenix Contact, Weidmuller, and probably others. If you look on the maker's or distributor's web sites, you will find a wide ...
Peter Bennett's user avatar
2 votes
Accepted

Trying to fix a mess with DC Power supply

I would crimp all the wires going to the same screw into a single spade terminal; all you need to do is make sure that the conductor cross sections are within the specified limits for the terminal you ...
vir's user avatar
  • 23.1k
2 votes

DIN rail terminal block resistor

Through-hole components are pretty easy to connect to standard DIN-rail mounted terminal blocks. Either screw or spring-clamp terminals would be fine. You can use 3- or 4-terminal blocks to have ...
Ben Miller's user avatar
1 vote
Accepted

Difference between two terminal blocks

What are the actual names of these two types of terminal blocks? In which cases, I should prefer one type over the other? The second image shows a rising clamp arrangement. Here's a view of the ...
Andy aka's user avatar
  • 473k
1 vote

DIN rail terminal block resistor

To convert a 4-20mA current output to a 2-10V signal, you can use an external resistor. Ohm's Law (V = I * R) can help determine the resistor value needed. For example, a 250-ohm resistor could ...
Alex's user avatar
  • 1,586
1 vote
Accepted

Barrier block vs. Lever wire splice for power distribution in a mobile robot

What you have there is a "barrier block" and a "lever wire splice". Can you share the pros and cons of the barrier block and lever wire splice? Between the two, the barrier block ...
Davide Andrea's user avatar
1 vote

What is the purpose of terminal blocks with a disconnecting neutral?

I can think of a few reasons one might want/need to isolate the neutral. Depending on the situation and local regulations, the neutral may or may not be regarded as safe to touch during maintenance ...
Peter Green's user avatar
  • 23.1k
1 vote

What is the terminal on the photo?

That is a card-edge connector, wide pitch (you can measure it). Quite popular in the 70-80. Well, the current PCIe and the memory slots in PCs are based on the same technology so it would be more ...
Lorenzo Marcantonio's user avatar
1 vote

What kind of terminal block is this?

The general term is "din rail terminals". Well-known manufacturers include Pheonix Contact, Weidmuller and Wago, there are probablly others. In addition to the regular terminals you will ...
Peter Green's user avatar
  • 23.1k
1 vote

Can a detachable terminal block be problematic for a 433 MHz whip antenna?

Even if the contact forms a thin non-conductive oxide layer, the proximity of the two contact halves will produce a capacitance of a few pF (worst case). At 1 MHz, a 1 pF capacitor has an impedance of ...
Andy aka's user avatar
  • 473k
1 vote

12V/5A power through DB9

Seeing that 5A is already relatively high a current to pass it trough a d-sub pin, I'd recommend at least not putting a large terminal block at the connector. Instead, I'd get a connector with solder ...
mmmm's user avatar
  • 1,789
1 vote

Do DIN rail mount interface relay modules with a "spare" terminal exist?

I've accepted @Jeroen3's answer, but for those looking for the actual product I've selected: Finder 39.51.0.024.0060 39 series, the MasterOUTPUT modules relay (not solid-state) push-in terminals 24V ...
sandyscott's user avatar
1 vote
Accepted

Using a terminal GND or VCC for multiple boards

If you do, the boards will experience a common mode voltage. The common mode voltage will be generated by the current from each of the boards and the resistance of the connector. If the loads are ...
Voltage Spike's user avatar
  • 88.8k